Contact Us

EX-proof Intirnsic Backup Battery

Product Overview:

LCX Power-GDC flame-proof & intrinsically-safe backup battery is special energy-storage backup unit for explosive hazardous locations.

It complies with GB3836 series explosion-proof standards, adopting independent heavy-duty flame-proof battery cavity plus intrinsically-safe output protection dual-safety design.

Adopt lithium-iron-phosphate battery cells, built-in high-reliability BMS battery management system with cell voltage, current and temperature real-time acquisition.

It provides DC backup energy for flame-proof & intrinsically-safe UPS, EPS, DC power supply and frequency converter.

The battery cavity is equipped with manual isolation switch and explosion-relief structure. The whole unit passes explosion-proof, pressure-resistant, damp-heat and anti-impact tests.

It features high safety, long cycle life, low self-discharge, suitable for coal-mine underground, petrochemical and other gas-dust explosive-risk working conditions。

Typical Applications:

· Coal-mine underground safety-monitoring, personnel-positioning system energy-storage backup unit

· Supporting backup energy for flame-proof & intrinsically-safe UPS, EPS, DC power supply and frequency converter

· Petrochemical, oil-gas field explosive-hazard-zone instrument emergency energy-storage power source

· Tunnel and mine-engineering explosion-proof control system standby battery pack

· Metallurgy & chemical-plant flammable-gas workshop safety equipment backup energy storage

· Mine refuge chamber, underground ring-network communication equipment emergency power-storage unit

LCX mining flameproof and intrinsically safe backup battery front view, explosion-proof battery for underground mine
LCX mining flameproof and intrinsically safe backup battery front view, explosion-proof battery for underground mine

Technical Specifications:

1. Explosion-proof Structure & Battery Design Independent heavy-duty flame-proof battery cavity, intrinsically-safe output protection circuit, explosion-proof mark Ex d[ib] I Mb. Equipped with manual isolation switch and special explosion-relief structure. Adopt lithium-iron-phosphate cells; capacity and voltage grade can be customized according to project demands.

2、Electrical Performance

· Multiple DC voltage grades optional, capacity range wide, support multi-box parallel expansion

· Low self-discharge rate, long cycle life

· High energy density, stable discharge platform

· Support long-term float-charge use, adapt to standby power-supply working condition

· Wide customizable backup duration according to load demands

3、Intelligent BMS Battery-management System Built-in independent BMS system, real-time monitor single-cell voltage, group voltage, charge-discharge current and cell temperature. Realize cell equalization, over-charge / over-discharge / over-current / over-temperature protection. Fault automatic locking function, prevent thermal runaway risk of battery pack。

4、Complete Multi-level Safety Protection Battery cavity over-pressure relief protection; charge-discharge over-current, short-circuit, over-temperature protection; cell over-voltage / under-voltage protection; intrinsically-safe output double-limit voltage-current protection. Fault-event record function. With reliable grounding terminal.

5、HMI & Communication Interface Local explosion-proof display window, real-time display battery pack voltage, current, remaining capacity, cell temperature and alarm information. Standard RS485 interface, Modbus protocol, support remote monitoring, data uploading for unattended hazardous sites.

6、Environmental-mechanical Adaptability Passive heat-dissipation structure; high-strength flame-proof enclosure, anti-shock, anti-vibration, damp-heat & corrosion-resistant. Operating temperature:-20℃ ~ +55℃. Adapt to underground mine, petrochemical sites with dust and corrosive gas。

LCX mining flameproof and intrinsically safe backup battery front view, explosion-proof battery for underground mine
LCX mining flameproof and intrinsically safe backup battery front view, explosion-proof battery for underground mine

Technical Parameters and Selection